Conductors: Class I (modified) bunched (8 and 6 AWG) and rope-bunched (4 AWG and larger) stranded tinned copper conforming to ASTM B-33 and Underwriters' Laboratories requirements. An opaque mylar tape shall be applied over the conductor to facilitate stripping.
Insulation: 90 ºC rated limited smoke, non-halogen, TelcoHyde 5221 conforming to Underwriters' Laboratories Standard 44 and Telcordia Specification GR-347-CORE, also UL and CSA 105 ºC AWN rated. The insulation has a limiting oxygen index of 35%.
Separator: On sizes 6 AWG and larger, a 1 mil clear mylar tape shall be applied over the insulation.
Covering: On all sizes a natural cotton braid conforming to UL requirements is applied overall. A section of completed cable has a limiting oxygen index of 35%.
Finish: A moisture resistant, flame retardant saturant and a coloured finisher is applied to the braid.
Surface Marking: Two sides of the cable shall be printed using an ink of contrasting colour and with the following information: "TelcoFlex IV/KS24194 L4 NON-HAL (SIZE) AWG (OR KCMIL) 600V. RHH/LS FT4 (UL) OR AWM 3578 VW-1 E18321 --- A.I.W. CORP --- LL8825 CSA AWM I B 105 ºC 600V. FT4 (YEAR) (SEQ. FTG. ON 1 SIDE)". For sizes 1/0 AWG and larger and "FOR CT USE" before "(UL)".
Testing: Physical and electrical tests in accordance with UL Standard 44 requirements.
Labels: UL tags and labels shall be applied to each reel.