Conductors: Class I (modified) bunched (8 and 6 AWG) and rope-bunched (4 AWG and larger) stranded tinned copper conforming to ASTM B-33 and Underwriters' Laboratories requirements. An opaque mylar tape shall be applied over the conductor to facilitate stripping.
Insulation: 90 ºC rated limited smoke, non-halogen, TelcoHyde 5221 conforming to Underwriters' Laboratories Standard 44 and Telcordia Specification GR-347-CORE, also UL and CSA 105 ºC AWN rated. The insulation has a limiting oxygen index of 35%.
Surface Marking: Two sides of the cable shall be printed using an ink of contrasting colour and with the following information: "TelcoFlex II/KS24194 L2 NON-HAL (SIZE) AWG (OR KCMIL) 600 V. RHH/LS FT4 (UL) OR AWM 3578 VW-1 E18321 --- A.I.W. CORP. --- LL8825 CSA AWM I B 105 ºC 600V. FT4-ST1 (YEAR) (SEQ. FTG. ON 1 SIDE)". For sizes 1/0 AWG and larger add "FOR CT USE" before "(UL)".
Testing: Physical and electrical tests in accordance with UL Standard 44 requirements.
Labels: UL tags and labels shall be applied to each reel.
*** NOTE: PLEASE CALL FOR EXACT PRICING AS PRICES LISTED MAY NOT BE CORRECT ***